Robot maintenance mode setup. This is part of the YRCP-MP4P PROFINET quick start guide.
Settings menu
The setup process requires the robot controller to be in maintenance mode
and a sufficient authorization level (management or higher).
Read more...
Activate maintenance mode:
- Power off
- Press (and hold) main menu
- Power on
- Release main menu when the beeping sound is heard (usually within a few seconds)
Change the authorization level:
- system » security » select
- select the desired level using ▼ ▲ » select
- enter the password and press enter
The YRCP-MP4P settings are located in menu SYSTEM » SETUP » OPTION BOARD » TRITON YRCP-MP4P
Information header
The blue header shows important information. Below an example for illustrative purposes:

- PROFINET
Activated features in the board. For PROFINET this can beIOControllerand/orIODevice. The required features will activated by the system software (see next steps). - DRV
Driver version. It is part of the system software but can be updated by overwriting the file on the SD card (/CP01/TRITON.DRV). - BOARD
Board firmware version. It is part of the board and can be updated using its webserver.
After finishing the setup in the next paragraphs, restart the robot controller and verify if the information header reflects the new setup.
Slave settings
The slave feature (IO-Device) is optional.
Adjust it to your needs (enable/disable).
Find the slave settings in menu SETUP » OPTION BOARD » TRITON YRCP-MP4P » IO DEVICE

- IO DEVICE
Enable/disable this feature. - IO SIZE (IN/OUT)
Number of bytes to exchange in both directions (e.g.32bmeans that there will be32binput and32boutput).
Master settings
This master feature (IO-Controller) is optional.
Adjust it to your needs (enable/disable).
Find the master settings in menu SETUP » OPTION BOARD » TRITON YRCP-MP4P » IO CONTROLLER

IO CONTROLLER
Enable/disable this feature.IO SIZE (IN/OUT)
Number of bytes to exchange in both directions (e.g.32bmeans that there will be32binput and32boutput).IOPS STATUS MONITOR
First register where the status bits of the slaves will be written to. In total, 32 registers will be written (one register per slave).ImportantMake sure these 32 registers are free (not used by other robot functions/applications).
PACK IO
Allows you to “pack” the data of each direction which means that there will be no unused space inbetween the data of the devices.Enabling it reduces the total packet size, at the cost of a less intuitive IO addressing (inputs and outputs of a device start at different byte addresses).
Disabling it guarantees a intuitive IO addressing (inputs and outputs of a device start at same byte address), at the cost of a larger total packet size.
TipRecommended setting: disable
PROFIsafe settings
The PROFIsafe slave feature is optional and only visible if the paid PROFIsafe option function is enabled by Yaskawa (FD parameter).
Find the PROFIsafe settings in menu SETUP » OPTION BOARD» TRITON YRCP-MP4P

PROFIsafe
Connects the PROFIsafe functionality to the board. Select the slot where you mounted the board.SAFETY IO SIZE
The usable packet size for PROFIsafe. This is fixed to 8 byte.F_CRC_LENGTH
This is the size of the PROFIsafe CRC header, and depends on the PROFIsafe profile your PLC is using. Older PLCs only support profilev2.4which uses a 3 byte CRC. However most modern PLCs support the newer profilev2.6.1, which uses a 4 byte CRC.ImportantPROFIsafe on YRCP-MP4P only supports 4 byte CRC (profile
v2.6.1).F_Dest_Address
This setting is defined by the customer/PLC programmer who integrates the PROFIsafe slave.PROFIsafe VIRTUAL COMM.
By setting this toVIRTUAL, you will be able to jog the robot even if the PROFIsafe master is not available. It is only used for shipping/commisioning and will automatically go back toSAFETYas soon as a PROFINET connection is detected.
Confirm settings
After enabling/disabling the master and/or slave features, some
settings inside the board will be adjusted.
This process starts as soon as you press ENTER to confirm the
settings and shows Transferring data to option /board ... at the bottom of
the screen while busy. It should take less than a minute.
The next screens will show the IO settings as you know from other fieldbus boards. Make sure to adjust the settings to your needs (images are for illustrative purposes only).


520 bits IO size in this example comes from: 1 byte status + 32 byte slave + 32 byte master.



If being asked for (at the bottom of the screen), perform a flash memory reset. Then restart the robot controller (maintenance mode) and verify if the information header reflects the new setup.
Tips
No items yet.
Troubleshooting
- Alarm 1241 [3901478]
This might be caused by a wrong setting for the PROFIsafe CRC header size .