Setup information for MotoLogix on Yaskawa YRC1000: MPiec PLC + EtherNet/IP fieldbus.

part number #215311

YRC1000.png
YRC1000 controller

Software version

This setup requires system software version: YAS4.26 (or newer).

Setup steps

  1. Install fieldbus board
    Mount the option board in the robot controller.

  2. Setup MotoLogix
    Activate the (paid) option function (by Yaskawa) and setup MotoLogix for the desired fieldbus and PLC architecture.

  3. Setup fieldbus
    Define the fieldbus data packet for MotoLogix.

  4. Set parameters
    Set the internal parameters required for MotoLogix usage.

The setup process requires the robot controller to be in maintenance mode and a sufficient authorization level (management or higher).

Read more...

Activate maintenance mode:

  1. Power off
  2. Press (and hold) main menu
  3. Power on
  4. Release main menu when the beeping sound is heard (usually within a few seconds)

Change the authorization level:

  1. system » security » select
  2. select the desired level using ▼ ▲ » select
  3. enter the password and press enter

Install fieldbus board

Yaskawa robot controllers use various fieldbus solutions:

typedescription
PCILarge form factor option board
PCIeCompact form factor option board
cpu boardSoftware option (uses the built-in LAN port)

EtherNet/IP CPU Board option function

This is a cpu board, using the built-in LAN port.
The function works exclusively with LAN2 (connector CN106).

product
CPU board

The activation of the EtherNet/IP CPU Board option function is not covered by this document. It is a separate setup process which includes licensing of the software stack.

Setup MotoLogix

  1. Open the MotoLogix option function settings: system » setup » option function » motologix

    motologix-option-function
    MotoLogix option function

    Customers: Please contact Yaskawa if the MotoLogix option function is not available in the list.
  2. Activate the MotoLogix option function:

    This requires Yaskawa authorization level and cannot be changed by the customer.

    motologix-settings
    MotoLogix settings

    If the system is setup for using safety fieldbus (FD288), the following error might occur when trying to activate MotoLogix:

    error-8113
    Error 8113

    Remedy:

    1. Disable FD288
    2. Activate MotoLogix
    3. Enable FD288
  3. Enter the settings:

    itemvalue
    FUNCTIONENABLED
    CONNECTION TYPEEthernet/IP(CPU Board)
    ENDIANNESSRockwell: LITTLE
    Yaskawa MPiec: BIG
    Customers can disable MotoLogix afterwards by setting FUNCTION to DISABLED.
    The ENDIANNESS (byte order) depends on the PLC cpu architecture.
  4. Use enter to confirm and leave the settings screen.

Setup fieldbus

Read more...
  1. Open the EtherNet/IP option function settings: system » setup » option function » EtherNet/IP(CPU Board)

    ethernetip-option-function1
    EtherNet/IP option function

    Customers: Please contact Yaskawa if the EtherNet/IP option function is not available in the list.
  2. Open the board settings:

    ethernetip-option-function2
    Open board settings

  3. Enter the settings:

    ethernetip-settings1
    Board used for MotoLogix

    itemvalue
    EtherNet/IP(CPU Board)USED (MotoLogix)
    The (optional) safety fieldbus setup is not covered by this document.
    Safety fieldbus does not require any additional settings for MotoLogix.
  4. Open the adapter screen and enter the settings:

    ethernetip-settings2
    EtherNet/IP adapter settings

    itemvalue
    ADAPTERENABLE
    INPUT SIZE + MotoLogixothers: 0 byte + 400 byte
    MPiec: 0 byte + 404 byte
    OUTPUT SIZE + MotoLogixothers: 0 byte + 436 byte
    MPiec: 0 byte + 440 byte
    CONFIGURATION SIZE10 word
    INPUT INSTANCE201
    OUTPUT INSTANCE200
    CONFIGURATION INSTANCE202
  5. Use enter (multiple times) to confirm this- and the following screens. Don’t make any changes in these following screens (keep default IO allocation).

IP address setting

The system ships with the following default address settings:

itemdefault setting
IP ADDRESS192.168.255.1
SUBNET MASK255.255.255.0
DEFAULT GATEWAY SETTINGNOT USED
Customers can adjust these settings to their needs.
Read more...
  1. Open the LAN option function settings: system » setup » option function » LAN interface setting

    lan-option-function
    LAN option function

  2. Adjust settings to your needs:

    LAN-settings
    LAN settings

    itemvalue
    IP ADDRESS SETTING(LAN2)MANUAL SETTING
    IP ADDRESS<IPv4 address>
    SUBNET MASK<subnet mask>
    DEFAULT GATEWAY SETTINGNOT USED / USED
    DEFAULT GATEWAY<gateway address>
  3. Use enter to confirm and leave the settings screen.

Parameter settings

Read more...
parametervalue
FD 67
FD 71
FD 1641
FD 2562
MF1G 455
RS 4751
S1C1G 570
S1D 1991
S1D 2290
S1D 2330
S1D 2562
S2C 2210
S2C 2442
S2C 3161
S2C 5410
S2C 5420
S2C 8691
S2C 10152
S2C 11390
S2C 11424
S2C 11470
S2C 12051
S2C 14191
S2C 15861
S2C 17021
S2C 17031
S2C 17041
S3C 138050
S3C 1385100
S3C 13872

Pages built with Hugo - 23 Apr 2024 11:54 CEST